P6-07 Trigger threshold speed error/speed monitoring

Setting range: 1.0 – 5.0 – 100%

This parameter specifies the maximum permitted speed error between the speed setpoint and the actual speed value.

The parameter is active in all operating modes (except V/f control) with and without encoder feedback. If the speed error lies outside the set limit value, the inverter switches off with speed error (SP-Err or Enc-02). When set to "100%", speed monitoring is deactivated.