P6-12 Speed holding time on inhibit

Setting range: 0.0 to 250 s

When the enable is deactivated, the inverter assumes the fixed setpoint speed 8 (P2-08) for the time defined here before the inverter stops along the deceleration ramp.

This function thus defines a time-delayed stop.

When set to "0.0", this function is deactivated.

INFORMATION

Setting this parameter to a value > 0 lets the inverter continue to run at the fixed setpoint speed for the set time after having removed the enable signal. It is important that you make sure that this operating mode is safe before you use this function.