P6-02 Automatic thermal management
Enables automatic thermal management. The inverter automatically reduces the output switching frequency in the event of an excessive heat sink temperature to reduce the risk of an overtemperature fault.
- 0: Deactivated (PWM fixed - depending on the setting in P2-24)
- 1: Activated (PWM varies, depending on the following table)
Heat sink temperature | Inverter behavior |
---|---|
70 °C | Automatic reduction from 16 kHz to 12 kHz. |
75 °C | Automatic reduction from 12 kHz to 8 kHz. |
80 °C | Automatic reduction from 8 kHz to 6 kHz. |
85 °C | Automatic reduction from 6 kHz to 4 kHz. |
90 °C | Automatic reduction from 4 kHz to 2 kHz. |
97 °C | Error message overtemperature |