Fault 35 Function activation

Subfault: 35.1

Description: Activation level – invalid activation key

 

Response: Emergency stop + output stage inhibit

Cause

Measure

The activation key was entered incorrectly.

Enter the activation key again.

The activation key was not created for this device.

Check the activation key.

When using a double axis, the activation key for the wrong instance was entered in the device.

Enter the activation key for the allocated instance.

Activation key entered for technology level in parameter "Application level – activation key".

Enter the activation key in the correct parameter.

Subfault: 35.2

Description: Application level too low

 

Response: Emergency stop + output stage inhibit

Cause

Measure

The activated software module requires a higher application level.

Activation key was entered for required application level. You can read the required level from the parameter "Application level – Required level".

Subfault: 35.3

Description: Technology level too low

 

Response: Emergency stop + output stage inhibit

Cause

Measure

An activated technology function requires a higher technology level.

Enter an activation key for the required technology level. You can find the required level in the parameter 8438.13 "Technology level – Required level".

Subfault: 35.4

Description: Technology level – invalid activation key

 

Response: Emergency stop + output stage inhibit

Cause

Measure

The activation key was entered incorrectly.

Enter the activation key again.

The activation key was not created for this device.

Check the activation key.

When using a double axis, the activation key for the wrong instance was entered in the device.

Enter the activation key for the allocated instance.

Activation key entered for application level in parameter "Technology level – activation key".

Enter the activation key in the correct parameter.