Fault 35 Function activation
Subfault: 35.1 Description: Activation level – invalid activation key | ||
---|---|---|
| Response: Emergency stop + output stage inhibit | |
Cause | Measure | |
The activation key was entered incorrectly. | Enter the activation key again. | |
The activation key was not created for this device. | Check the activation key. | |
When using a double axis, the activation key for the wrong instance was entered in the device. | Enter the activation key for the allocated instance. | |
Activation key entered for technology level in parameter "Application level – activation key". | Enter the activation key in the correct parameter. |
Subfault: 35.2 Description: Application level too low | ||
---|---|---|
| Response: Emergency stop + output stage inhibit | |
Cause | Measure | |
The activated software module requires a higher application level. | Activation key was entered for required application level. You can read the required level from the parameter "Application level – Required level". |
Subfault: 35.3 Description: Technology level too low | ||
---|---|---|
| Response: Emergency stop + output stage inhibit | |
Cause | Measure | |
An activated technology function requires a higher technology level. | Enter an activation key for the required technology level. You can find the required level in the parameter 8438.13 "Technology level – Required level". |
Subfault: 35.4 Description: Technology level – invalid activation key | ||
---|---|---|
| Response: Emergency stop + output stage inhibit | |
Cause | Measure | |
The activation key was entered incorrectly. | Enter the activation key again. | |
The activation key was not created for this device. | Check the activation key. | |
When using a double axis, the activation key for the wrong instance was entered in the device. | Enter the activation key for the allocated instance. | |
Activation key entered for application level in parameter "Technology level – activation key". | Enter the activation key in the correct parameter. |