Fault 26 External fault
Subfault: 26.1 Description: Terminal | ||
---|---|---|
| Response: External fault | |
Cause | Measure | |
Fault message about external fault source. | Programmable via 8622.5 (default: application stop (with output stage inhibit)). |
Subfault: 26.3 Description: Power section emergency shutdown | ||
---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
Power section requested external emergency shutdown because it detected critical fault. | Contact SEW‑EURODRIVE Service. |
Subfault: 26.4 Description: External braking resistor fault | ||
---|---|---|
| Response: Response to external braking resistor fault | |
Cause | Measure | |
The temperature switch of the external braking resistor connected to a terminal detected an error. | – Check the resistor mounting position. – Clean the resistor. – Check the configuration of the resistor. – Install a larger resistor. – Check the trip switch settings. – Optimize the travel cycle so that less regenerative operation energy arises. – Check the settings of the storage unit discharge function in the MOVIKIT® software module. |