Fault 31 Thermal motor protection
Subfault: 31.1 Description: Temperature sensor wire break – motor 1 | ||
---|---|---|
| Response: Application stop + output stage inhibit | |
Cause | Measure | |
Connection to temperature sensor of motor 1 interrupted. | Check the wiring of the temperature sensor. |
Subfault: 31.2 Description: Temperature sensor short circuit – motor 1 | ||
---|---|---|
| Response: Application stop + output stage inhibit | |
Cause | Measure | |
Short circuit in connection with temperature sensor of motor 1. | Check the wiring of the temperature sensor. |
Subfault: 31.3 Description: Temperature sensor overtemperature – motor 1 | ||
---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
Temperature sensor of motor 1 signals overtemperature. | – Allow the motor to cool down. – Check for motor overload. – Check whether the correct temperature sensor KY (KTY) was parameterized instead of PK (PT1000). |
Subfault: 31.4 Description: Temperature model overtemperature – motor 1 | ||
---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
Temperature model of motor 1 signals overtemperature. | – Allow the motor to cool down. – Check for motor overload. – Check whether the correct temperature sensor KY (KTY) was parameterized instead of PK (PT1000). |
Subfault: 31.7 Description: UL temperature monitoring | ||
---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
Temperature model of active motor signals overtemperature. | Check for motor overload. |
Subfault: 31.8 Description: Communication timeout temperature sensor – motor 1 | ||
---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
Communication with temperature sensor is disrupted, e.g. via MOVILINK® DDI. | Check the cabling. |
Subfault: 31.9 Description: Temperature too low at temperature sensor – motor 1 | ||
---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
Short circuit in connection with temperature sensor of motor 1. For long cables, a short circuit can be misinterpreted as a voltage value of a low temperature. | Check the wiring of the temperature sensor. | |
Temperature signaled by temperature sensor of motor 1 below -50 °C. | – Check if a KTY temperature sensor is installed in the motor but the parameterization has been carried out for a PT1000 temperature sensor. – Heat the motor. |