Fault 7 DC link
Subfault: 7.1 Description: Overvoltage in the DC link | ||
---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
Maximum permitted DC link voltage exceeded. | – Decrease deceleration. – Check the supply cable to the braking resistor. – Check the configuration of the braking resistor (resistance value). |
Subfault: 7.2 Description: DC link discharge failed | ||
---|---|---|
| Response: Warning | |
Cause | Measure | |
DC link voltage level not dropped below discharge threshold within discharge time. | Contact SEW‑EURODRIVE Service. |