Fixed setpoints – acceleration 1, 2

This menu item offers the following setting options:

  • Application limit – acceleration DT1 and DT2
  • Fixed setpoint – acceleration 1 and 2 DT1
  • Fixed setpoint – acceleration 1 and 2 DT2

INFORMATION

In the factory setting, only the application limits are effective. For the fixed setpoints to take effect, you must change the parameter Maximum acceleration – source (index 8377.21) to the value 1F20A2 hex (fixed setpoints acceleration). For information on changing the parameter, refer to chapter Access to parameters via index.
The values can be specified with a maximum of 8 integer places and 2 decimal places in the system unit min-1.

7-segment display

Parameters

Index

Application limit – acceleration DT1

8357.12

Fixed setpoint – acceleration 1 DT1

8354.40

Fixed setpoint – acceleration 2 DT1

8354.42

Application limit – acceleration 1 DT2

8358.12

Fixed setpoint – acceleration 1 DT2

8354.41

Fixed setpoint – acceleration 2 DT2

8354.43

"Setting fixed setpoints for acceleration" sequence