Startup for hoist function
- First perform a motor startup in VFC speed control according to chapter Startup with asynchronous motors with VFC speed control.
- Activate the brake control for lifting applications P4-12 = 1.
- Set the ramp times for P1-03 and P1-04 as short as possible.
- Set the minimum speed P1-02 to at least 1.5 times the rated motor slip.
- If no sensor is used for protecting the braking resistor, you can optionally use the following parameters for protection against overtemperature of the braking resistor. However, only a sensor provides adequate protection.
- P6-19: Braking resistance value
- P6-20: Braking resistance power
- Observe the direction of rotation of the motor:
- Positive speed on the display = Raise hoist
- Negative speed on the display = Lower hoist