3-wire control
The function is activated via the digital input function selection P1-15 = 21.
The 3-wire control principle determines the control.
The enable and direction of rotation signals of the inverter then respond in an edge-controlled way.
- Connect the start key <CW> with NO contact to digital input DI1.
- Connect the start key <CCW> with NO contact to digital input DI3.
- Connect the stop key as NC contact to digital input DI2.
If you connect <CW> and <CCW> at the same time, the drive decelerates along the rapid stop ramp P2-25.
Additional information