P2-30 Analog input 1 format

  • 0: 0 – 10 V / unipolar voltage range
  • 1: 10 – 0 V / unipolar voltage range
  • 2: -10 – 10 V / bipolar voltage input
  • 3: 0 – 20 mA / current input
  • 4: t4 – 20 mA / current input
  • 5: r4 – 20 mA / current input
  • 6: t20 – 4 mA / current input
  • 7: r20 – 4 mA / current input

"t.." indicates that the inverter shuts down when the signal is removed while the inverter is enabled. t4 – 20 mA, t20 – 4 mA

"r.." indicates that the inverter moves along a ramp to P2-08 when the signal is removed while the inverter is enabled. r4 – 20 mA, r20-4 mA