P2-33 Analog input 2 format/motor protection
- 0: 0 – 10 V/unipolar voltage input
- 1: 10 – 0 V/unipolar voltage input
- 2: PTC-th / motor thermistor input TF/TH (trigger threshold 2.5 kΩ)
- 3: 0 – 20 mA/current input
- 4: t4 – 20 mA/current input
- 5: r4 – 20 mA/current input
- 6: t20 – 4 mA/current input
- 7: r20 – 4 mA/current input
- 8: ty-b/KTY84 motor temperature sensor (120 °C trigger, 100 °C reset)
- 9: ty-F/KTY84 motor temperature sensor (155 °C trigger, 125 °C reset)
- 10: ty-H/KTY84 motor temperature sensor (180 °C trigger, 160 °C reset)
- 11: Pt-b/PT1000 motor temperature sensor (120 °C trigger, 100 °C reset)
- 12: Pt-F/PT1000 motor temperature sensor (155 °C trigger, 125 °C reset)
- 13: Pt-H/PT1000 motor temperature sensor (180 °C trigger, 160 °C reset)
"t.." indicates that the inverter shuts down when the signal is removed while the inverter is enabled. t4 – 20 mA, t20 – 4 mA