Procedure

The state machine is in the "Switch-on inhibited" state.

1.

For startup, see Startup preparations and Reference travel – 0x8300.

  • Set the state machine to the "Switch-on inhibited" state.

The module shows the status "Switch-on inhibited".

2.

Set the following parameters:

3.

Send the "Switch off" command 0x8100-01 – Control word, bit 3 – 0: x110.

The module shows the status "Ready to switch on."

4.

Send the "Switch on" command 0x8100-01 – Control word, bit 3 – 0: 0111.

The module shows the "Switched on" status.

5.

Send the "Enable operation" command 0x8100-01 – Control word, bit 3 – 0: 1111.

The module shows the status "Operation enabled". The drive is now ready for travel commands.