SS1-t safety sub-function with MOVISAFE® CS..A
The SS1-t safety sub-function monitors the parameterized time delay and triggers the STO safety sub-function once the time delay has elapsed. To implement the SS1-t safety sub-function, the ramp monitoring must be set to "none" and the final state to "STO" in the SSx instance.
If the Inverter control parameter is set to "active", activating the SS1-t safety sub-function results in the activation of the FCB13 Application stop drive function in the inverter.
If the Inverter control parameter is set to "Not active", the inverter is not controlled.
Additional information