Adjusting the maximum test duration for load with unknown capacitance
In order to determine the "Maximum test duration" parameter (Index 8705.2) for a load with unknown capacitance at a safe digital output (F-DO..), proceed as follows:
- Select one of the two safe digital outputs, F-DO00 or F-DO01. Connect the load according to the selected connection type and set the "Connection type".
- Set the "Maximum test duration" parameter (Index 8705.2) to the maximum value of 5000 μs.
- Interconnect the selected output for at least 10 seconds.
- Form the maximum value from the following values for the selected output:
- Value of display parameter "Maximum duration test pulse A" (Index 8703.37)
- Value of display parameter "Maximum duration test pulse B" (Index 8703.8)
- Block the selected output for at least 10 seconds.
- Form the maximum value from the following values for the selected output:
- Formed maximum value from step 4
- Value of display parameter "Maximum duration test pulse A" (Index 8703.37)
- Value of display parameter "Maximum duration test pulse B" (Index 8702.8)
- In order to specify the "Maximum test duration" value (Index 8705.2), add a reserve of 500 μs to the maximum value determined in step 6.