P4-06 Torque reference/limit value source
Function of the parameter, depending on operating mode/motor control
Operating mode/motor controller | Torque limit value (% of rated motor torque) | Torque reference (% of rated motor torque) | Current limit (% of rated motor current) |
---|---|---|---|
P4-01 = 0, 3, 6, 7, 8 | X | – | – |
P4-01 = 1, 4 | – | X | – |
P4-01 = 2 | – | – | X |
- 0: P4-07 defines the torque reference/limit.
- 1: Analog input 1 determines the torque reference/limit. (0 – 100% of P4-07)
- 2: Analog input 2 determines the torque reference/limit. (0 – 100% of P4-07)
- 3: Fieldbus process data word determines the torque reference/limit (0 – 100% of P4-07)
- 4: Master/slave (make setting in slave):
- The slave inverter takes over the torque reference/limit from the master inverter.
- 5: PID output determines the torque reference/limit (0 – 100% of P4-07)