P4-02 "Auto tune"

  • 0: Locked
  • 1: Enable

Only enable the inverter after you have entered all nominal motor data correctly in the parameters. You can also start the automatic measuring procedure "Auto tune" manually with this parameter after entering the motor data.

After a reset to the factory setting, the measuring procedure starts automatically after the first enable and takes up to 2 minutes depending on the control type.

INFORMATION

After changing the nominal motor data, auto tune has to be started again. The inverter must not be in "inhibit" mode.