Startup at gateway
- Connect the gateway as described in chapter Electrical installation.
- Reset all settings of the gateway to the factory setting.
- If required, set all connected inverters to SBus MOVILINK® mode as described in chapter Parameter settings for the inverter. Assign unique SBus addresses (≠ 0!) and set a baud rate matching the gateway (default = 500 kBaud).
- Set DIP switch AS (auto-setup) on the DFx/UOH gateway from "OFF" to "ON" to perform an auto-setup for the fieldbus gateway.
- The "H1" LED on the gateway lights up repeatedly and then goes off completely. When the "H1" LED is lit, the gateway or one of the inverters at the SBus has not been wired properly or has not been taken into operation properly.
- Refer to the relevant DFx manual for information on how to establish fieldbus communication between DFx/UOH gateway and bus master.