P9-30 Positive limit switch CW

Setting range: OFF, din-1, din-2, din-3, din-4, din-5, din-6, din-7, din-8

The parameter defines the digital input for the positive limit switch. The switch must be wired as an NC contact with wire break monitoring. As soon as the limit switch is tripped, the inverter reduces the speed along ramp P1-04 to 0 Hz.

As long as the enable persists at the inverter, the inverter stays enabled at 0 Hz.

The status of the limit switch is also depicted in the status word.