P7-09 Overvoltage current limit
Setting range: 0.0 – 1.0 – 100%
This function discharges the DC link in generator mode. The maximum motor speed is limited here to 120% of P1-01 or 120% of P1-09 (the highest limit value is used in each case).
When set to "0.0", this function is deactivated.
Procedure:
- The motor with high inertia is decelerated. Regenerative energy flows back to the inverter.
- The DC link voltage increases and reaches the UDCmax level.
- To discharge the DC link, the inverter delivers current (P7-09) and the motor accelerates again.
- The DC link voltage falls below UDCmax again.
- The motor is further decelerated.