Device replacement with MOVI-C® for MOVIDRIVE® technology

The MOVI-C® system provides the option of storing the application data set of the inverter and the data set of the safety option on the memory module in the inverter.

The following steps must be performed for the actual device replacement:

  1. Switch off the device to be replaced.
  2. Remove the plugged-in memory module from the device.
  3. Remove the pluggable safety key from the CS..A safety option.
  4. Replace the device (including MOVISAFE® CS..A safety option).
  5. Insert the memory module removed in step 2 back into the replaced device.
  6. Insert the safety key removed in step 3 back into the replaced safety option.
  7. Carry out a functional test. The checking of all parameters is omitted.

The inverter automatically detects the device replacement and loads the application data set into the MOVISAFE® CS..A safety option. The localized key data set on the pluggable safety key ensures that the correct application data set has been loaded. The MOVISAFE® CS..A safety option is then in the same state that it was in before the device replacement. This means that if the MOVISAFE® CS..A safety option was in the "Accepted" state before the device replacement, it will be in the "Accepted" state again after device replacement. In order to ensure correct connection of the sensors and actuators, a function test of the safety option is required in the case of automatic device replacement function.

INFORMATION

Check the referencing of the CSA31A after having replaced a MOVISAFE® CSA31A safety option.