Fault responses

The following table describes the following fault responses:

Fault response

Description

No response

The inverter ignores the event

Warning with self-reset

The inverter issues a warning message with self-reset. The fault is automatically reset after the cause of fault is eliminated.

Warning

The inverter issues a warning message.

Application stop (with output stage inhibit)

The inverter stops with the deceleration set for the application limit.

Parameter set 1 Index 8375.0-13

Parameter set 2 Index 8375.8-13

If n = 0: Brake "applied" and output stage "off".

Application stop (with output stage inhibit) with self-reset

Emergency stop (with output stage inhibit)

The inverter stops with the set emergency stop deceleration.

Parameter set 1 Index 8375.0-20

Parameter set 2 Index 8375.8-20

Emergency stop (with output stage inhibit) with self-reset

Inhibit output stage with self-reset

The output stage is deactivated and the brake is applied.

Inhibit output stage

Self-reset means: Eliminating the cause of the fault results in acknowledgment of the fault. The inverter automatically resumes the operation before the fault occurred. The drive restarts automatically.