X2330: AC 400 V output and +24 V output

The following table provides information about this connection:

Function

X2330 AC 400 V output and 24 V output (OUT)

Connection type

Han® Q4/2, female, by HARTING

(Current load max. 30 A, max. 24 A for UL)

Connection diagram

Assignment

Contact

Function

1

L1

Line connection, phase L1

2

L2

Line connection, phase L2

3

L3

Line connection, phase L3

4

Res.

Reserved

11

+24 V

DC 24 V input for backup mode (OUT)

12

0V24

0V24 reference potential for backup mode (OUT)

PE

PE

Protective earth connection