0x8100-01 – Control word
Index-Sub | Type | RW | Default | Range of values | Unit | Description |
|---|---|---|---|---|---|---|
0x8100-01* | U16 | R/W** | 0 | 0 – 65535 | Control word |
You can use the control word to change the current status of the motor controller or reset all error bits:
|
Bit combinations
3 | 2 | 1 | 0 | Bit 3 to 0 – Control drive status |
|---|---|---|---|---|
x | 1 | 1 | 0 | Switch off |
0 | 1 | 1 | 1 | Switch on |
1 | 1 | 1 | 1 | Switch on and enable operation |
x | 0 | 0 | x | Switch off voltage |
0 | 1 | 1 | 1 | Inhibit operation |
1 | 1 | 1 | 1 | Enable operation |
x | 1 | 1 | x | Rapid stop |
15 – 8 | 7 | 6 – 4 | Bit 15 to 4 – Reset error bits |
|---|---|---|---|
Reserved | 0 → 1 | Reserved | Edge 0 – 1 resets all error bits in "0x8100-06 – Bit bar error" |