Fault 23 Power section

Fault: 23.4 (1704hex | 5892dec)

Description: Hardware fault

 

Response: Output stage inhibit

Cause

Measure

A fault was detected on a component of the power section.

– Check for short circuit/ground fault at the output of the inverter.

– Reduce the line capacity at the output of the inverter.

– If the fault occurs repeatedly, contact SEW‑EURODRIVE Service.

Fault detected on switched-mode power supply.

Check the DC 24 V supply voltage.

Fault detected at the gate driver of a power semiconductor.

Contact SEW-EURODRIVE Service.