Transferring the parameter set using MOVITOOLS® or the DBG keypad

  1. Remove the MOVIMOT® inverter from the connection box.
  2. Check the connection of the MOVIMOT® inverter.
    • See chapter "Electrical installation".
  3. Set all mechanical control elements identical to the reference device.
  4. Place the MOVIMOT® inverter onto the connection box and screw it in place.
  5. Connect the PC/laptop or the DBG keypad to the MOVIMOT® inverter.
  6. Connect the 24 V supply of the MOVIMOT® inverter.
  7. When using a PC/laptop, start MOVITOOLS® MotionStudio and integrate the MOVIMOT® inverter in MOVITOOLS®.
  8. Transfer the entire parameter set of the MOVIMOT® reference unit to the MOVIMOT® inverter.
  9. Check the functionality of the MOVIMOT® drive.
  10. Disconnect the PC/laptop or the DBG keypad from the MOVIMOT® inverter.
  11. NOTICE! Loss of the specified degree of protection if the screw plugs on the f1 setpoint potentiometer and the X50 diagnostic interface are not installed or not installed correctly. Damage to the MOVIMOT® inverter. Make sure the screw plug of the setpoint potentiometer has a seal and screw it in.