Permitted number of connection or cable disconnection points
When using a hybrid cable or a solo coaxial cable on the MOVILINK® DDI interface, a maximum of 4 connection or cable disconnection points are permitted. The connection points that are implemented directly on the inverter or in the drive by means of FAKRA connectors are not included in the count. Communication errors can occur if there are more than 4 connection or cable disconnection points.
Examples
- Cable from inverter to motor with M23 connector KD1: 1 plugging position
- Cable from inverter to motor with M23 connector KD1 and 1 extension cable M23 at both sides: 2 plugging positions
- Cable from inverter to motor with M23 connector KD (hybrid cable gland without plug connector): 0 plugging positions