"BF" LED
This LED indicates the status of the PROFINET interface. The state includes communication link, bus error and process data configuration.
Status | Possible cause | Measure |
---|---|---|
Off | Error-free operating state. The PROFINET device is exchanging data with the PROFINET controller (Data Exchange state). | – |
Red Permanently lit | Connection to the PROFINET controller has failed. Bus communication has been interrupted. | Check the PROFINET connection of the PROFINET device. Check all the cables in the PROFINET network. |
The PROFINET controller is not in operation. | Check the PROFINET controller. | |
The PROFINET device does not detect a PROFINET baud rate. | Check the configuration of the PROFINET controller. | |
Yellow Permanently lit | There is a connection to the PROFINET controller, but the configuration of the PROFINET network is faulty. The following errors may have occurred:
| Check the configuration of the PROFINET controller. |