Supply cable for braking resistor

Use only shielded or twisted cables.

The cable cross section depends on the tripping current IF.

The nominal voltage of the cable must be at least U0/U = 450 V/750 V.

The maximum permitted cable length between the inverter/power supply module and the braking resistor is 100 m.

The temperature resistance of the braking resistor cables must be ≥ 90 °C.

When the braking resistor is connected to its protection device, the shield of the supply cable must be routed via an additional shield terminal.