Inputs/outputs

NOTICE

Damage to the digital inputs and digital outputs.
The digital inputs and digital outputs are not electrically isolated. Incorrectly applied voltages can damage the digital inputs and digital outputs.
  • Do not apply a voltage  > DC 30 V to the digital inputs and digital outputs.
  • The digital inputs and outputs are dimensioned according to IEC 61131‑2.

If you route the cables outside the control cabinet, you have to shield them irrespective of the length.

When connecting the shielding, ensure equipotential bonding.