Line connection
- The line contactor must always be located upstream of the line filter.
- Use only line contactors of utilization category AC-3 (EN 60947-4-1) or higher.
- Do not use the line contactor for jog mode, but only for switching the inverter on and off.
- Observe the required dimensioning of the cable cross sections for UL-compliant installation.
For the terminal assignment for line connection of the various sizes, refer to chapter "Terminal assignment".
Observe a minimum switch-off time of 10 s for the inverters. Do not switch the power on more than once per minute.
NOTICE
Non-compliance with the minimum switch-on/switch-off times
Inverter damage.
- Observe a minimum switch-off time of 10 s before switching on the power supply again.
- Do not switch on the supply system more than once per minute/every 2 minutes.