Parameter 600
Terminal configuration
Parameter P600 can only be changed if all digital inputs are set to "0".
Use this parameter to select the configuration of digital input terminals.
The following tables show the functions of the digital input terminals in relation to the control setpoint source and the terminal configuration:
|
Control / setpoint source "Binary" | ||||
|---|---|---|---|---|
|
Terminal |
Digital input terminals | |||
|
f1/f2 X6:7,8 |
L |
R | ||
|
0: |
Terminal configuration 1 |
Setpoint switch mode "0" signal: Setpoint f1 "1" signal: Setpoint f2 |
CCW/Stop "0" signal: Stop "1" signal: Counterclockwise rotation |
CW/Stop "0" signal: Stop "1" signal: Clockwise rotation |
|
1: |
Terminal configuration 2 |
Selection of fixed setpoints Fixed setpoint n0: signal "0", "0" param. P170 Fixed setpoint n1: signal "0", "1" param. P171 Fixed setpoint n2: signal "1", "0" param. P172 Fixed setpoint n3: signal "1", "1" param. P173 |
Enable/stop "0" signal: Stop "1" signal: Enable | |
|
2: |
Terminal configuration 3 |
Setpoint switch mode "0" signal: Setpoint f1 "1" signal: Setpoint f2 |
/external error "0" signal: Ext. Error "1" signal: No Ext. Error |
Enable/stop "0" signal: Stop "1" signal: Enable |
|
Control setpoint source "RS485" | ||||
|---|---|---|---|---|
|
Terminal- |
Digital input terminals | |||
|
f1/f2 X6:7,8 |
L |
R | ||
|
0: |
Terminal configuration 1 |
No |
CCW/Stop "0" signal: Stop "1" signal: Enable CCW |
CW/Stop "0" signal: Stop "1" signal: Enable CW |
|
1: |
Terminal configuration 2 |
No |
No function |
Enable/stop "0" signal: Stop "1" signal: Enable CW and CCW operation |
|
2: |
Terminal configuration 3 |
No |
/external error "0" signal: Ext. Error "1" signal: No ext. Error |
Enable/stop "0" signal: Stop "1" signal: Enable CW and CCW operation |