Parameter 600

Terminal configuration

Parameter P600 can only be changed if all digital inputs are set to "0".

Use this parameter to select the configuration of digital input terminals.

The following tables show the functions of the digital input terminals in relation to the control setpoint source and the terminal configuration:

Control / setpoint source "Binary"

Terminal
configuration

Digital input terminals

f1/f2 X6:7,8

L X6:9,10

R X6:11,12

0:

Terminal configuration 1

Setpoint switch mode

"0" signal: Setpoint f1

"1" signal: Setpoint f2

CCW/Stop

"0" signal: Stop

"1" signal: Counterclockwise rotation

CW/Stop

"0" signal: Stop

"1" signal: Clockwise rotation

1:

Terminal configuration 2

Selection of fixed setpoints

Fixed setpoint n0: signal "0", "0" param. P170

Fixed setpoint n1: signal "0", "1" param. P171

Fixed setpoint n2: signal "1", "0" param. P172

Fixed setpoint n3: signal "1", "1" param. P173

Enable/stop

"0" signal: Stop

"1" signal: Enable

2:

Terminal configuration 3

Setpoint switch mode

"0" signal: Setpoint f1

"1" signal: Setpoint f2

/external error

"0" signal: Ext. Error

"1" signal: No Ext. Error

Enable/stop

"0" signal: Stop

"1" signal: Enable

Control setpoint source "RS485"

Terminal-
configuration

Digital input terminals

f1/f2 X6:7,8

L X6:9,10

R X6:11,12

0:

Terminal configuration 1

No
function

CCW/Stop

"0" signal: Stop

"1" signal: Enable CCW

CW/Stop

"0" signal: Stop

"1" signal: Enable CW

1:

Terminal configuration 2

No
function

No function

Enable/stop

"0" signal: Stop

"1" signal: Enable

CW and CCW operation

2:

Terminal configuration 3

No
function

/external error

"0" signal: Ext. Error

"1" signal: No ext. Error

Enable/stop

"0" signal: Stop

"1" signal: Enable CW and CCW operation