Brake control (control via RS485 + binary control)

Mechanical brake controlled by MOVIMOT® inverter:

  • Terminals X1:13, X1:14, and X1:15 in the MOVIMOT® connection box are assigned to the brake coil of the mechanical brake. You must not connect an additional braking resistor to terminals X1:13 and X1:15.
  • The relay is switched as ready signal relay (standard function).

Mechanical brake controlled by the relay output or the BEM/BES option:

WARNING

Risk of crushing due to unintentional startup of the drive caused by incorrect settings of the DIP switches S2/5 – S2/8. Failure to comply with chapter Use of the relay output for additional functions 7, 9, 12, and 13 can result in the brakes releasing.
Severe or fatal injuries.
  • A braking resistor (BW..) must be connected to terminals X1:13 and X1:15 in the MOVIMOT® connection box. Terminal X1:14 is not assigned.
  • Relay K1 acts as brake control relay. This means that the ready signal function is no longer available.