Fault 9 Control mode
Subfault: 9.2 Description: Requested operating mode not possible with active control mode | ||
|---|---|---|
| Response: Emergency stop + output stage inhibit | |
Cause | Measure | |
The current FCB activated an operating mode. The active control mode does not support this operating mode, for example "positioning control" or "torque control" with V/f control mode. | – Use a control mode that supports the required operating mode. Connect an encoder if necessary. – Select an operating mode that is supported by the current control mode. | |
Subfault: 9.12 Description: Manipulated value of current controller not plausible | ||
|---|---|---|
| Response: Emergency stop + output stage inhibit | |
Cause | Measure | |
Voltage measurements for A-side and/or B-side are faulty. | – Acknowledge the fault. – If the fault occurs repeatedly, replace the device. For further support, contact SEW‑EURODRIVE Service. | |