MDP92A-0250 power supply module
Using a braking resistor is only required if generator mode is reached during operation and the regenerative energy cannot be absorbed completely by the energy storage units in all operating states. A braking resistor is not required if the device is operated solely in motor mode.
Alternatively, the braking resistor can also be used to discharge the energy storage unit. This is useful, for example, if the energy storage unit must be discharged quickly and easily for system reasons or for servicing purposes.