Process output data

The following table shows the process output data from the PLC to the inverter for control via the fieldbus.

Word

Bit

Function

PO 1

Control word

0

Enable/emergency stop

1

Enable/application stop

2

Reserved

3

Release brake (without enable)

4

Jog positive

5

Jog negative

6

Reserved

7

Start/stop with fieldbus ramp

8

Error reset

9

Reserved

10

Activate drive train 2

11

Reserved

12

Deactivate SW limit switches

13

Activate output stage inhibit

14

Activate standby mode

15

MOVIKIT® Handshake In

PO 2

Setpoint speed/maximum speed

0 – 15

User unit

PO 3

Acceleration

0 – 15

User unit

PO 4

Deceleration

0 – 15

User unit

PO 5

Digital outputs

(For control via process data, see chapter Digital inputs/digital outputs)

0

DO 00/DIO 01 (output)

1

DO 01/DIO 02 (output)

...

...

3

DO 03

...

...

PO 6

Setpoint application mode

0 – 15

Operating mode (see chapter Operating modes)

PO 7

Reserved

0 – 15

 

PO 8

Reserved

0 – 15

 

Default assignment

The assignment of the following process data words depends on the additional function used:

Word

Bit

Function

PO 9

Reserved or control word for torque limit (optional)

0 – 15

 

PO 10

Setpoint torque/maximum torque

0 – 15

In 0.1% nominal motor torque

  • In torque control operating mode (800), the process data word specifies the setpoint torque.
  • In the other operating modes, the process data word specifies the torque limit. The torque limit becomes effective when the control word for the torque limit has been activated in the [Basic settings] and when it is controlled accordingly.

INFORMATION: For the behavior of the torque limit in all operating modes observe the additional information in chapter Variable torque limit via process data.

When using the variable jerk time:

Word

Bit

Function

PO 9

Setpoint jerk time

0 – 15

Specified jerk time in ms

PO 10

Reserved or control word for torque limit (optional)

0 – 15

 

PO 11

Setpoint torque/maximum torque

0 – 15

In 0.1% nominal motor torque

  • In torque control operating mode (800), the process data word specifies the setpoint torque.
  • In the other operating modes, the process data word specifies the torque limit. The torque limit becomes effective when the control word for the torque limit has been activated in the [Basic settings] and when it is controlled accordingly.

INFORMATION: For the behavior of the torque limit in all operating modes observe the additional information in chapter Variable torque limit via process data.