Replacing a defective auxiliary contact
Part number | Designation | Use |
|---|---|---|
29663288 | Contact element Q1.1 | Separation of ESMinus |
29663288 | Contact element Q1.2 | Disconnector feedback |
If the auxiliary contact Q1.1 is defective, also check the following components for correct function:
- Auxiliary contact Q1.2
- Disconnector Q1
- Fuse F3
If the auxiliary contact Q1.2 is defective, also check the following components for correct function:
- Auxiliary contact Q1.1
- Disconnector Q1
- I/O module
Procedure:
- Disconnect the electrical connections.
- Remove the defective auxiliary contact.
- Mount and install the new auxiliary contact in reverse order.