MDP92A-0100.. power supply module and MDE90A-0200.. DC/DC-converter module
MOVI-DPS®
energy storage unit
If a MOVI-DPS® external energy storage unit, which is not installed in the same control cabinet, is connected to one of the following devices, a ferrite sleeve must be attached to the connection cables. The ferrite sleeve is enclosed with the devices MDP92A-0100.. and MDE90A-0200.. as a standard accessory.
Connect the external energy storage unit to the following terminals:
- MDP92A-0100..: X12
- MDE90A-0200..: X12
- MDC90A-0120..: X4_B
- MDC92A-0125..: X4_B

[1] | Ferrite sleeve |
[2] | Cable tie for securing the ferrite sleeve to the sheet metal |
ESS
energy storage unit
Note that ESS energy storage systems must be connected with a cable cross section of 35 mm², according to the specifications in the operating instructions of the energy storage systems. Connect an ESS energy storage unit directly to DC link connection X4. To do so, use the connection set with part number 28261666, which is used for two-row setup.
If an ESS external energy storage unit is connected to one of the following devices, a ferrite sleeve must be attached to the connection cables. The ferrite sleeve must be ordered separately (part number 25665308). The one enclosed to the devices is not suitable for this purpose.
- MDP92A-0100..: X4
- MDE90A-0200..: X4

[1] | Ferrite sleeve |
[2] | Cable tie for securing the ferrite sleeve to the sheet metal |