Error 9 Control mode
Error: 9.2 (0902hex | 2306dec) Description: Operating mode not possible with active control mode | ||
|---|---|---|
| Response: Output stage inhibit (standard) | |
Cause | Measure | |
The active control mode does not support the operating mode selected in the current FCB. EXAMPLE: The V/f control mode does not support the FCB "Position control" or "Torque control". | – Use a control mode that supports the required operating mode. If necessary, connect an encoder. or – Select an operating mode that is supported by the current control mode. | |
Error: 9.12 (090Chex | 2316dec) Description: Manipulated value of current controller not plausible | ||
|---|---|---|
| Response: Output stage inhibit (standard) | |
Cause | Measure | |
Voltage measurements for A-side and/or B-side are faulty. | – Acknowledge the fault. – If the error occurs repeatedly, replace the device. For further support, contact SEW‑EURODRIVE Service. | |