Pulsed voltage supply and detection of short circuits
For information about parameterization and operating principles, refer to chapter "Startup".
If line diagnostics is used for the safe digital input F-DI00, both input terminals (F-DI00_A and F-DI00_B) are assigned to the F‑SS0 sensor supply.
Line diagnostics can only be activated for both input terminals together.
If line diagnostics is not used (e.g. for sensors with OSSD output), the sensors can be supplied by F-SS0 or by another +24 V supply that has the same ground reference as the safety option.