Extended storage

The following table shows the time intervals and maintenance work which must be taken into consideration during extended storage of the devices:

Modules

Time interval

Maintenance

MDP92A

MDS90A

Every 2 years

Line connections: Connect the devices to the line voltage for 5 minutes.

MDC90A

Connect the device to the DC 800 V operating voltage for 10 minutes.

MDE90A

No measures required

DANGER

Uncovered power connections.
Severe or fatal injuries from electric shock.
  • Fit the touch guards to the devices, see chapter "Touch guards".
  • Attach the closing covers according to the regulations, see chapter "Touch guards".
  • Never start up the devices unless touch guards and closing covers have been fitted.