Line connection

For the terminal assignment for line connection, refer to the chapter "Terminal assignment".

  • The use of a line contactor is optionally possible. Use only line contactors of utilization category AC-3 (EN 60947-4-1) or higher.
  • The line contactor must be located upstream of the line filter.
  • Do not use the line contactor for jog mode, but only for switching the power supply module on and off. The FCB 20 "Jog" must be used for jog mode.
  • Observe the required dimensioning of the cable cross-section for UL-compliant installation.