Installing touch guards and closing covers
All modules of the application inverter are equipped with touch guards [1] and the first and last modules of the axis system have closing covers [2]; see the following figure. If the axis system contains a master module, the closing cover [2] must be attached only to the final module in the axis system.
For the MDP92A-.. power supply module, connector X1 and for the DC/DC converter MDE90A-.., connector X12 must always be plugged in and screwed tightly. These connectors are part of the protection against accidental contact that is necessary to achieve IP20 degree of protection.
With master module

Without master module

[1] | Touch guard |
[2] | Closing cover |
Install all touch guards [1] after installation work.
- Insert the closing cover [2] into the touch guard [1].
- Install the touch guard [1] on the respective module. Insert the screws and tighten them securely with the specified tightening torque.
Install one closing cover [2] each on the first and final modules of the axis system. The closing covers prevent any contact with the DC link. Two closing covers are included with each power supply module.

WARNING

Missing touch guards and closing covers
Severe or fatal injuries from electric shock
- Install all touch guards.
- Install closing covers on the first and final module in the axis system.