Installation requirements

Check that the following conditions have been met:

  • The information on the nameplate of the device corresponds to the line voltage.
  • The device is undamaged (no damage caused by transport or storage).
  • The ambient temperature corresponds to the specification in the operating instructions and the nameplate.
  • The device must not be installed in the following ambient conditions:
    • Potentially explosive atmosphere
    • Oils
    • Acids
    • Gases
    • Vapors
    • Radiation
  • For special designs: The device is designed in accordance with the actual ambient conditions.
  • Trained specialists perform the installation.
  • The information provided in the technical data and the permitted conditions for the operating location of the device are observed.
  • The minimum clearance and the required gaps for using a mounting plate are complied with. For more information, refer to chapter Minimum clearance.
  • Only mount the device using the mounting options intended for it.
  • The selection and dimensioning of the mounting and locking elements are in line with the applicable standards, the technical data of the devices and the local requirements.
  • The bore dimensions are calculated in line with the respective type of fixture. For more information, see chapter "Mechanical installation".
  • The mounting and locking elements fit into the existing bores, threads and countersinks.
  • All display and actuator elements are visible and accessible after installation.
  • The device is positioned in a way that it will not collide with other components or design elements along the travel path.
  • Fasten the device so that it is not exposed to shocks or vibrations during operation that exceed the mechanical conditions described in the technical data.