Project planning example
The following project planning example shows the project planning of the 24 V voltage supply:
- The digital inputs of the inverters are controlled with external DC 24 V voltage.
- The VO24 auxiliary voltage output on the inverter does not output voltage if the inverter is only supplied with DC 24 V backup voltage via the gateway.
- A network of 4 MOVITRAC® classic inverters is established.
- A gateway is plugged into the 1st inverter.
- Communication modules are plugged into the other 3 inverters.
In this case, only the gateway is supplied with an external DC 24 V voltage. All other devices are supplied by the gateway via the ribbon cable.
This results in a power demand of 4 × 1 W + 1 × 3 W + 3 × 0.5 W = 8.5 W.