Installing the line filter
Observe the following information:
- Install the line filter close to the inverter but outside the minimum clearance for cooling. The line filter must not be heated by the exhaust air of the application inverter.
- Mount the line filter and inverter on a shared mounting plate. Make sure they are connected over as large an area as possible and with good conductivity.
- Observe the following minimum distances and mounting positions for convection cooling:
Permitted mounting position | Distance in mm | ||
|---|---|---|---|
On the side | Downward | Upward | |
3 and 4 | 0 | 100 | 100 |
- Observe the following permitted mounting positions during installation: