Installing the line choke
Observe the following information:
- Install the line choke close to the inverter but outside the minimum clearance for cooling. The line choke must not be heated by the exhaust air of the inverter.
- Install the line choke before the line filter.
- Observe the following minimum distances and mounting positions for convection cooling:
Permitted | Distance in mm | ||
|---|---|---|---|
On the side | Downwards | Upwards | |
1, 2, 3, 4 | 0 | 100 | 100 |
- Observe the following permitted mounting positions during installation: