Mounting the output filter

Observe the following information:

  • Install the output filter close to the inverter but outside the minimum clearance for cooling. The exhaust air from the output filter must not heat the supply air to the inverter.
  • Mount the output filter and inverter on a shared mounting plate. Make sure they are connected over as large an area as possible and with good conductivity.
  • Observe the following minimum distances and mounting positions for convection cooling:

Permitted mounting position

Distance in mm

On the side

Downward

Upward

3 and 4

0

100

100

  • Observe the following permitted mounting positions during installation: