Mounting the output choke
Observe the following information:
- Install the output choke close to the inverter but outside the minimum clearance for cooling. The exhaust air of the output choke must not heat the supply air of the inverter.
- Mount the output choke and inverter on a shared mounting plate. Make sure they are connected over as large an area as possible and with good conductivity.
- Observe the following minimum distances and mounting positions for convection cooling:
Permitted mounting position | Distance in mm | ||
|---|---|---|---|
On the side | Downward | Upward | |
3 and 4 | 0 | 100 | 100 |
- Observe the following permitted mounting positions during installation: