Deactivating the EMC capacitors
For the inverters of sizes 0S and 0L, the EMC capacitors are disabled as follows:
- Disconnect the inverter from the power supply.
- Check if the inverter is de-energized.
- Remove all connectors.
- If applicable: Remove the filler plug at terminal position X6.
- Remove the CDM11A diagnostic module.
- Remove the electronics shield terminal.
- Remove the retaining screws at the front center of the housing.
- Remove the housing.
- Destruction of the device. Touch the printed circuit board only at the edge, never at electronic components.
- Remove both retaining screws [1] from the printed circuit board.
- Insert both retaining screws [1] into the supplied plastic insulation pieces [2].

- Re-fasten the retaining screws [1] to the printed circuit board.
- Close the unit.
- Identify the device by marking the respective point on the nameplate.